IMPACT OF THE CHARACTERISTICS OF OVERHEAD GROUND WIRES ON THE CURRENT REDUCTION FACTOR, AND THEIR EFFECT ON THE CHANGE OF GROUNDING SYSTEM POTENTIAL

  • Mario Havranek University of Osijek, Faculty of Electrical engineering
  • Tomislav Strinić University of Osijek, Faculty of Electrical engineering
  • Goran Knežević University of Osijek, Faculty of Electrical engineering
Keywords: surface potential, current reduction factor, grounding, touch voltage, step voltage

Abstract

This paper shows the impact of the characteristics of overhead ground wires on the change of grounding system potential in a power system substation during a single line to ground fault. The touch and step voltages can be affected by changing the overhead ground wire radius. The calculation of the current reduction factor depending on the size of the overhead ground wire is also presented. Furthermore, simulations of the grounding system potential, the surface potential as well as the touch and step voltages of a study case have been made using CYMGRD simulation software, which has implemented the IEEE 80-2000 standard (IEEE Guide for Safety in AC Substation Grounding). The power system substation observed in the simulation includes two incoming 110 kV transmission lines with two 110 kV bus bars as well as 35 kV and 10 kV bus bars. The entire grounding system of the substation is comprised of a conducting net aligned horizontally, and mutually interconnected by vertically placed conducting rods. The simulations performed show the change of the observed potential values for a given size of the overhead ground wire. In order to determine the maximum fault current that can occur in the observed
substation (which is needed for calculation of the substation ground potential), a single-phase short circuit is simulated on the 110 kV bus bars, using the simulation software DIgSILENT Power Factory.

Downloads

Download data is not yet available.

References

L.H. Chena, J.F. Chena, T.J. Liang, W.I. Wang: Calculation of ground resistance and step voltage for buried ground rod with insulation lead, Electric Power System Research 2008, Vol.78., pp. 995–1007.

D. Prasad, H.C. Sharma: Significance of Step and Touch Voltages, International Journal of Soft Computing and Engineering 2011, Vol.1(5), pp. 193–197.

J. Ma, F. P. Dawalibi: Modern Computational Methods for the Design and Analysis of Power System Grounding, Proceedings of International Conference on Power System Technology, p.p. 122-126, 18-21 August 1998.

http:// www.cyme.com

http:// www.digsilent.de

Franjo Majdandžić: Groundings and grounding systems, Graphis, pp. 133–143, 2004.

P.L. Buccheri, S. Mangione: Analysis of ground fault current distribution along nonuniform multi-section lines, Electric Power System Research 2008, Vol. 78(9), pp. 1610–1618.

IEEE: IEEE Guide for Safety in AC Substation Grounding, The Institute of Electrical and Electronics Engineers, p.p. 1–192, 2000.

J. Schlabbach: Short circuit current, The Institution of Engineering and Technology, pp. 172–179, 2005.

Published
2024-04-18
How to Cite
Havranek M., Strinić T., & Knežević G. (2024). IMPACT OF THE CHARACTERISTICS OF OVERHEAD GROUND WIRES ON THE CURRENT REDUCTION FACTOR, AND THEIR EFFECT ON THE CHANGE OF GROUNDING SYSTEM POTENTIAL. Journal of Energy Technology, 6(1), 19-32. https://doi.org/10.18690/jet.6.1.19-32.2013
Section
Articles

Most read articles by the same author(s)